2.) A synchronous generator is 3-phase, wye-connected, and rated 1,131 KVA, 2.4 KV, 0.90 lagging power factor. What is the output current (in Amperes) from the generator at rated full load?
Hint: Draw the 1∅ equivalent of the 3∅. Note that 1,131 KVA is a 3∅ specification. 2.4 kV is a line voltage. Assume line voltage is 2.4k